The requirement of 1 large UPS to field, environment
(1) the horniness cement that equipment perch field should be ” of “ industry type horizontal ground, if use antistatic mobile floor, need to be on the base that measures considering the average negative charge of the floor, be designed even according to the weight of UPS make the bracket for installing equipment.
To most and large UPS, the cable of its level type falls to next entering model. The ventilated mouth taking energy of life of UPS machine ark is located in the front of machine ark or flank, gas outlet is in the upside of machine ark or from the back. For this, when installing UPS, good cable of requirement user precondition lays ground channel. The deepness of ground channel is 40 Cm left and right sides. When the user uses bridge cable to lay, should choose cable to be aspirant on piece model type.
(2) UPS power supply system should be installed in have drafty, cool, humidity to be mixed not high in having the clean airy of the condition that do not have dirt to run an environment. Although general UPS place allows temperature limits is ℃ of 0 ℃ ~ 40 between. However, if the condition allows when, answer to be environmental temperature control under 35 ℃ . The working temperature that UPS manufacturer recommends is ℃ of 20 ℃ ~25. Humidity control is in 50% the left and right sides is advisable. In addition, should not deposit in the room that runs in UPS explode combustibly, easily or have caustic gas or liquid article.
(3) forbidden in installing UPS the working environment in the dust that has metallic conductivity, can bring about equipment to produce short circuit breakdown otherwise. Unfavorable also put UPS approaching heat source point.
Origin: Pole of uncut jade of Mian Lai white
(4) whether does the UPS accumulator team that matchs without giving thought to deserve to have take temperature compensatory charger. To ensure the service life of accumulator group, should be the temperature control of accumulator room between ℃ of 20 ℃ ~25.
(5) the controls side to must protect hold 50mm airspace of UPS, there is 100mm space from the back, in order to make sure UPS is drafty. Before UPS due and enough operation space. Through carrying out a proof, UPS had better not rely on wall installation, the distance of left and right sides having 1m should keep between UPS and wall, in order to facilitate the maintenance of UPS. About the specific installation data of all sorts of UPS, consult please the user manual that brings randomly.
(6) when the user is designing the ventilated and cooling system of UPS computer room, consult please below the data of the power comsumption that concerns all sorts of UPS and ventilation.